Hyphen today is one of the most preferred and trusted name in House wires. It has emerged as first choice and gained reputation & confidence of consultants, architects and real estate developers.
Hyphen has built up a reputation for commercial foresight and solid integrity. Tested and supervised by experienced engineers in sophisticated labs, our wires have earned a name for themselves in both Indian and international markets.
Specification: Click Here to view Specification for House Wiring and industrial cables. |
Reference Specification | IS : 694-1990 |
Voltage Grade | 1100 Volts |
Conductor |
Aluminium: E.C. Grade Aluminium as per flexibility class 1 &2 of IS : 8130-1984
Copper: Electrolytic Grade Bare Annealed Copper as per flexibility class 1,2 & 5 of IS : 8130-1984 |
Insulation |
PVC Type A of IS : 5831-1984 for Conductor Temperature 700C PVC Type C of IS : 5831-1984 for Conductor Temperature 850C |
Colour of Insulation | Cable for fixed installation |
Single Core Wire & Cables | Red, Yellow, Blue, Grey, Green, White or any colour as per customer's requirement. |
Two Core Cables | Red & Black |
Three Core Cables | Red, Yellow & Blue |
Four Core Cables | Red, Yellow, Blue & Black |
Colour of Insulation | Flexible Wires, Cables & Cords |
Single Core Wires & Cables | Red, Yellow, Blue, Black, Grey, Green, White or any colour as per customer's requirement |
Two Core Cables | |
Three Core Cables | Red, Black & Green |
Four Core Cables | |
Five Core Cables | |
Sheath |
PVC Type ST-1 of IS : 5831-1984 for Conductor Temperature 700C PVC Type ST-2 of IS : 5831-1984 for Conductor Temperature 850C |
1.) Non Weatherproof Cables : | Black or any colour as per Customer's requirement |
2.) Weatherproof Cables : | Black Only |
Tolerance on Thickness of Insulation
Tolerance on Thickness of Insulation |
The smallest of the measured values of thickness of insulation shall not fall below the nominal value specified in the relevant tables by more
than (0.1 mm + 0.1 t1) Where t1 = Nominal Thickness of Insulation in mm. |
Tolerance of Thickness of Sheath |
The smallest of the measured values of thickness of sheath shall not fall below the nominal value specified in the relevant tables by more
than (0.2 mm + 0.2 ts) Where ts = Nominal Thickness of Sheath in mm. |
Laying up of core for 2, 3 and 4 core cables | The cores are be laid together with a suitable right hand lay. |
Flat 2 and 3 core cable |
The cores are laid side by side. In case of 2 core flat cables with Earth continuity conductor the core and the E.C.C are laid side by side in the same plane with E.C.C. occupying the central position.
|